Flange check valves are essential components in pipeline systems, designed to prevent medium backflow. Proper installation and maintenance are critical for optimal performance. Below are key technical points:
Installation Essentials
Positioning
Install vertically with the valve bonnet facing upward (except for horizontal swing-type designs).
Ensure 5x pipe diameter of straight upstream/downstream sections for laminar flow.
Flange Connection
Use PN10/PN16 standard flanges (per GB/T 9119).
Align gaskets properly and tighten bolts crosswise in 3 stages (30%-70%-100% torque).
Flow Direction
Arrow markings on valve body must match medium flow direction.
Verify disc movement is unobstructed before pressure testing.
Sealing Integrity
Apply graphite spiral-wound gaskets for high-temperature/pressure applications.
Conduct helium leak test if handling hazardous media.
Maintenance Protocol
Routine Inspection
Quarterly checks for:
✓ Disc movement (should swing freely)
✓ Seal leakage (<0.1% of rated flow)
✓ Bolt tension (retorque if loosening exceeds 10%)
Cleaning
Flush with clean water/compressed air every 6 months.
Remove debris from seat ring and disc guide rails using nylon brushes.
Lubrication
For swing-type valves: Apply food-grade silicone grease to hinge pins annually.
For lift-type valves: Lubricate stem threads with EP2 lithium grease.